《6667 - AQ Compute's BCN 1 - OCP Ready v2 for Hyperscale.pdf》由会员分享,可在线阅读,更多相关《6667 - AQ Compute's BCN 1 - OCP Ready v2 for Hyperscale.pdf(13页珍藏版)》请在三个皮匠报告上搜索。
1、Jaime Comella,AQ ComputeAQ Computes BCN 1 OCP Readyv2 for HyperscaleAQ Computes BCN 1 OCP Readyv2 for Hyperscale Core and Shell Forecasted Q3 2026Jaime Comella,AQ ComputeEMEA DEPLOYMENTSOF OCP RECOGNIZED SOLUTIONSDC hubDC hubSubmarinecables landing stationBarcelona metropolitan area50 MW+data center
2、 campus1st data center building under construction,planned for Q2-Q3 2026 AQ-BCN project and campusAQ-BCN project and campusLoading bayGENs+TXsPOWERMODPOWER M COOLINGITE COOLINGAQ-BCN1 site access and logistics1CAMPUS SITE ACCESS&LOGISTICSATTRIBUTEPARAMETERRESULT1.0SITE ACCESS1.0-AVehicular Access i
3、nc.truck circulation1.Roadway access to loading dock to allow for a trailer 12.2m(40)WheelbaseOptimum1.0-BBuilding Access 2.Covered road level loading dock and threshold free access(notes required)Acceptable1.0-CDelivery pathway,Loading dock to storage room1.2.75m(108in)H x 1.6m(63in)W unobstructed
4、access and threshold freeOptimum1.0-DDelivery pathway,Goods in to IT Technical Space 1.2.75m(108in)H x 1.6m(63in)W unobstructed access and threshold freeOptimum1.0-ECorridor floor rolling load1.680 kg(1500 lb/ft2)(6.67 kN)slab on gradeOptimum1.0-FUnboxing/pre-staging/storage area floor uniform load1
5、.1221 kg/m2(250 lb/ft2)(11.97 kN/m2)slab on gradeOptimum1.0-GUnboxing/pre-staging/storage area floor concentrated load1.680 kg(1500 lb/ft2)(6.67 kN)slab on gradeOptimum1.1ACCESS CONTROLS&MONITORING1.1-ASite perimeter fence 1.2.43m(96in)H with perimeter intrusion detection system(PIDS)Optimum1.1-BSit
6、e security lighting1.Site lighting with backup powerOptimum1.1-CMain Security Checkpoint(or check in location)1.Staffed 24/7Optimum1.1-DLevels of security to gain access to IT Technical Space1.3 (site perimeter-building perimeter-secure corridor and IT Technical Space)Optimum1.1-EVideo surveillance