《用于管理OCP液冷设备的统一Redfish方案.pdf》由会员分享,可在线阅读,更多相关《用于管理OCP液冷设备的统一Redfish方案.pdf(11页珍藏版)》请在三个皮匠报告上搜索。
1、Mick JonesUnified Redfish Schema for Managing OCP Liquid Cooling Equipment Unified Redfish Schema for Managing OCP Liquid Cooling Equipment Mick Jones-VertivLIQUID COOLINGDefine a unified schema under DMTF Redfish for management of all OCP Liquid Cooling Equipment:CDUs,Immersion;Tank and Enclosed Ch
2、assisCold Plate;BMCs,aggregation and control loops,Rear Door HXFacilities;FWS,valves,inline sensors,Chillers#,etcHeat Re-use;Tanks/Reservoirs,Heat Exchangers,Pumps,etcCreate mockup(examples)of the expected output from the compliant management interfaces and management systemsContribution schema and
3、mockups to Redfish Forum for inclusion in Redfish releaseCreate/extend OCP Interoperability ProfilesPurpose of WorkstreamThermal Equipment Schema amendments v1.0 were released in 2023.1Release includes schema files and mockupHas 80%coverage of all resources and relationships discussed(v1.0)Thermal E
4、quipment Schema amendments v1.0+were released in 2023.3Adds cooling redundancy resourcesThermal Equipment Schema amendments ongoingIterate schema based on feedbackMessage registriesInterop Profiles and mock-upsProgressPublished in Redfish v2023.1Enhanced in v2023.3In sustaining mode nowSchemaTargeti
5、ng release in Redfish v2024.4(end of year)New messages exclusively for Liquid CoolingExamples:Flow ratePressureFan SpeedPump SpeedLeak detectionMessage Registries New baseline and device profiles based of new Redfish Service Baseline Defines standard interface for a LC device Milestones:Device/syste