当前位置:首页 > 报告详情

多热源冲击式冷板解决方案.pdf

上传人: 明**** 编号:1011506 2025-12-21 19页 2.30MB

1、Multi-heat-sources Jet Impingement Cold Plate SolutionsCooler MasterMulti-heat-sources Jet Impingement Cold Plate SolutionsYogesh Fulpagare,PhDDeputy Chief Engineer/Cooler Master Corp.David ChenDeputy Chief Engineer/Cooler Master Corp.COOLING ENVIRONMENTSOutline 54321Motivation of new type jet impin

2、gement developmentPOC of distribution plate in impingement cold plate designSimulation of multi-dimensional distribution plateDIOJIC cold plate design concept and validation resultsConclusionMotivation of new type jet impingement developmentPrevent the fluid from pre-heating before flowing through t

3、he heat sourcesHigher flow rate leads to higher pumping power requirement in typical designErosion issues due to higher flow rate and flow velocityMake more uniform temperature distributionDistribution Plate POC Cold Plate Design and Sample Setting Heating element dimensionsPositions of thermocouple

4、sThermal Test VehiclePOC Cold plate650W650W250W250WExperimental Test ResultsThermal PerformanceTemperature DistributionFlowFlow Rate L/minRate L/minGeometry and Flow Field(CP based on H100)1D2DVelocity Magnitude(m/s)0.5 LPM 0.5 LPM1D distribution plate consists of a row of outlet holes that jet liqu

5、id toward the central hot spot.2D distribution plate consists of a matrix of outlet holes that spreads liquid toward the skived fin.1D H100 Jet Impingement Cooling Cold PlateTDP=1000 WTIM thermal conductivity=8W/mKTIM Thickness=0.1 mmCoolant=PG25Flow rate=0.5 to 2 LPMFlow Rate(LPM)0.50.7511.52Rth(K/

6、W)0.0290.0250.0230.0200.019Pressure Drop(PSI)0.1980.4170.7180.8512.774Maximum Temperature(C)69.0164.7262.5660.1858.79Minimum Temperature(C)60.0655.7853.5451.1749.82Average Temperature(C)64.8260.7958.6556.2954.912D H100 Jet Impingement Cooling Cold PlateTDP=1000 WTIM thermal conductivity=8W/mKTIM Thi

word格式文档无特别注明外均可编辑修改,预览文件经过压缩,下载原文更清晰!
三个皮匠报告文库所有资源均是客户上传分享,仅供网友学习交流,未经上传用户书面授权,请勿作商用。
本文主要介绍了Cooler Master公司开发的多热源喷射冲击冷板解决方案。关键点如下: 1. **动机**:为防止流体在流经热源前预热,提高流动速率,减少泵送功率需求,解决侵蚀问题,并实现更均匀的温度分布。 2. **设计验证**:通过1D和2D分布板的模拟和实验,验证了设计。 3. **实验结果**:1D和2D冷板在流量为0.5至2 LPM时,热阻分别降低至0.019和0.021 K/W。 4. **压力和热性能**:2D分布板通过平行流动降低了63.6%的压力降和62.5%的泵送功率。 5. **DIOJIC设计**:与斜片式鳍片冷板相比,DIOJIC-PINFIN-CP冷板泵送功率降低了15.7%,热阻降低了16%。 6. **与文献比较**:DIOJIC-CP在热阻和泵送功率方面优于其他喷射冲击冷板设计。