1、Elizabeth Langer,CPCTravis Gaskill,NvidiaUNIVERSAL QUICK DISCONNECT(UQD)VERSION 2 UPDATESUNIVERSAL QUICK DISCONNECT(UQD)Version 2 UpdatesElizabeth Langer,CPCTravis Gaskill,NvidiaLIQUID COOLINGWorkstream StakeholdersUQD Workstream Charter The Universal Quick-Disconnect Specification 1 was released to
2、 the OCP community in 2020,with the UQDB(Blindmate)specification following in 2021.As the ecosystem expands,gaps in the initial version have been exposed that hinder rapid adoption at scale The purpose of this workstream is to update the UQD/UQDB v1 specification such that gaps in requirements and p
3、erformance are resolved,ambiguity is removed,and true interoperability is defined and achievable.Background&Purpose Unification of the UQD/UQDB Specs into a singular document Addition of Hybrid use case:UQDB socket and UQD plug mating configuration Uniform dimensioning and tolerance approach across
4、sizes and configurations Performance and Interoperability requirements refinement Established process for specification governanceKey Deliverables Streamlined adoption and application stability of UQD within OCP ecosystemSuccess Metric(s)1 OCP Spec,“Universal Quick Disconnect UQD Specification”,Inte
5、l,2020Leverage UQD Plug in blindmate configurationSame plug used in handmate configurationAlign connected length of UQD and Hybrid configurations to standardize“panel to panel”distances in applicationUQD plug overall length was undefined in v1Provide guidance for capturing full range of tolerances-r
6、ecommend system level compliance mechanism(s)*New in V2*|Hybrid ConfigurationOverdrive example:coil spring can compress when parts hit hard stop to absorb variation in panel distancesUndefined in v1BB standard length dimension to control panel distance when mated with UQDB socket(undefined in v1)GG