当前位置:首页 > 报告详情

Murata Powering Open Compute Forward - Murata.pdf

上传人: 2*** 编号:139837 2023-08-27 17页 1.49MB

1、15 March 2023Copyright Murata Manufacturing Co.,Ltd.All rights reserved.3/15/20231Murata Powering Open Compute ForwardKevin GeroSr.Product Marketing Mgr.Murata SubsystemsPrague April 20232Copyright Murata Manufacturing Co.,Ltd.All rights reserved.3/15/2023Facebook initiated the Open Compute Project

2、in 2011:“with a mission to apply the benefits of open source and open collaboration to hardware and rapidly increase the pace of innovation in,near and around the data centers networking equipment,general purpose and GPU servers,storage devices and appliances”Murata entered the Open Compute Project

3、market with the release of our first 12V,21”1OU shelf in early 2017In those days 12V was the way to go.6 across 18kW/15kW N+1 redundantWith an RMU/controllerMuratas first Open Compute ProductsMurata Powering OCP Forward3Copyright Murata Manufacturing Co.,Ltd.All rights reserved.3/15/20233kW PSU-MWOC

4、P74-3000-12-RMInput 100 to 277Vac or 192 to 400Vdc(HVDC)Output+12.3V/244A;12Vsb/2.5A(Vsb internal to shelf)Power3030W max 180Vac1830W max 180VacEfficiencyTitaniumRide through 12mSCoolingForced air,internal fan(towards connectors)RedundantN+1 or N+N redundantOperating temp 0 50oCPower density30.4W/in

5、3TopologyMulti-Phase LLCMechanical550mm(L)x 73.5mm(W)x 40mm(H)(21.65”x2.89”x1.57”)OthersInput&output reporting&PMBus interfaceSafety Approvals UL/CSA,CB,CCC,BSMI,CE4Copyright Murata Manufacturing Co.,Ltd.All rights reserved.3/15/20233.2kW ATS PSU MWOCP74A3200-A-RM5Copyright Murata Manufacturing Co.,

6、Ltd.All rights reserved.3/15/2023 Then a customer wanted a 19”version.The still wanted 18kW/15kW N+1 redundant They wanted 6 AC outlets in the back of the shelf for 3 outlets with redundant AC sources.Single or Dual Power Zone solutions in a single rack High power density and efficiency Support Sing

word格式文档无特别注明外均可编辑修改,预览文件经过压缩,下载原文更清晰!
三个皮匠报告文库所有资源均是客户上传分享,仅供网友学习交流,未经上传用户书面授权,请勿作商用。
Murata Power Systems在2017年加入了Open Compute Project(OCP),推出了首款12V、21英寸的1OU架。他们的产品支持高达18kW或15kW的N+1冗余,具有远程管理单元(RMU)和多功能相位 LLC 拓扑结构。随后,Murata开发了符合OCP ORV3标准的54V、18kW N+1电源架,具有80Plus Titanium效率等级,支持热插拔,并可通过Ethernet和串行控制台接口进行管理。 Murata还开发了适用于19英寸EIA架或21英寸OCP架的50.5V、54V、48V ORV3兼容电源架,以及正在开发中的48V ORV3电池备份单元(BBU),预计将于2024年2月展示原型。这些产品使用Murata制造的锂离子电池模块,在线路电压低于47.5V时提供48V的备份电源,持续4分钟。 此外,Murata的电源和电源架产品适用于浸没式冷却方案,已与多个客户合作,并在与Submer合作开发一款3U ORV3架,带有15个50.5V/54V电源,总功率超过54kW,专为浸没式冷却设计。